Page 80 - CPVC Fire Sprinkler Products Installation Instructions & Technical Handbook
P. 80

78 APPENDIX A - PIPE FITTINGS
ASTM CPVC Fitting Socket Dimensions U.S. Units
C
DFEBA
  Nominal Inches
Pipe A B C D Minimum
Nominal
 Size Socket Socket Minimum Minimum Wall ANSI Entrance Bottom Socket Inside Thicknesses
Inches Diameter Diameter Depth Diameter E
F
0.141
0.166
0.175
0.250
0.275
0.345
0.375
  3/4 1.058
1 1.325
1 1/4 1.670
1 1/2 1.912
2 2.387
2 1/2 2.889
3 3.516
1.046 0.719
1.310 0.875
1.655 0.938
1.894 1.375
2.369 1.500
2.868 1.750
3.492 1.875
0.740 0.113
0.990 0.133
1.335 0.140
1.446 0.220
1.881 0.218
2.250 0.276
2.820 0.300
       ASTM CPVC Fitting Socket Dimensions Metric Units
C
DFEBA
Nominal Nominal Millimeters
   Pipe A B C D Minimum
Size Socket Socket Minimum Minimum Wall
DN Entrance Bottom Socket Inside Thicknesses
Diameter Diameter Depth Diameter E F
  DN20 26,88 26,60 18,30
DN25 33,70 33,30 22,23
DN32 42,42 42,04 23,82
DN40 48,60 48,11 34,93
DN50 60,63 60,20 38,10
DN65 73,40 72,90 44,45
DN80 89,31 88,70 47,63
18,80 2,90 3,60
25,15 3,40 4,22
33,91 3,60 4,50
36,73 5,60 6,40
47,80 5,54 7,00
57,20 7,00 8,80
71,63 7,62 9,53
       