Page 55 - CPVC Fire Sprinkler Products Installation Instructions & Technical Handbook
P. 55

TECHNICAL DATA 53
  Table R - One Point of Restraint
  Nominal Pipe Size ANSI Inches DN
    “N” Less than 100 psi (6,9 bar)
   “N” Greater than 100 psi (6,9 bar)
 3⁄4
DN20
1
DN25
1 1⁄4
DN32
1 1⁄2 - 3
DN40 - DN80
0’-9” (0,23 m)
1’-0” (0,30 m)
1’-4” (0,41 m)
2’-0” (0,61 m)
0’-6” (0,15 m)
0’-9” (0,23 m)
1’-0” (0,30 m)
1’-0” (0,30 m)
    MAX.
RESTRAINT ONE-POINT
One-Point Vertical Restraint
MAX.
RESTRAINT ONE-POINT
NN
 3
  Table S - Two Points of Restraint
  Nominal Pipe Size ANSI Inches DN
    “M” Less than 100 psi (6,9 bar)
   “M” Greater than 100 psi (6,9 bar)
 3⁄4
DN20
1
DN25
1 1⁄4
DN32
1 1⁄2 - 3
DN40 - DN80
Two-Point Vertical Restraint
4’-0” (1,22 m)
5’-0” (1,52 m)
6’-0” (1,83 m)
7’-0” (2,13 m)
ANY DISTANCE
RESTRAINT TWO-POINT
3’-0” (0,91 m)
4’-0” (1,22 m)
5’-0” (1,52 m)
7’-0” (2,13 m)
    M MAX.
 














































   53   54   55   56   57