Page 23 - CPVC Fire Sprinkler Products Installation Instructions & Technical Handbook
P. 23

LISTINGS & APPROVALS 21
Table B - Ground Cover
  Nominal Pipe Size ANSI Inches DN
3
DN80 and Under
Trench Width Inches (mm)
8 (203,2)
Ground Cover Minimum Inches (mm)
 Light Traffic
12 - 18 (305,0 - 457,2)
Heavy Traffic
30 - 36 (762,0 - 914,4)
   Loop
Length 10° 20° 30° 40° 50° 60° 70° 80° 90° 100°
2
 Table C1 - U.S. Units
Maximum Temperature Variation, °F Between Time of Solvent Welding and Final Use
   DEFLECTED PIPE
 OFFSET
LOOP LENGTH
OFFSET
     2 LOOP LENGTHS
   Temperature Variation, °F
 Feet
Offset- Inches
  20 3 4 5 5 6 6 7 7 8 8
50 7 9 11 13 14 16 17 18 19 20
100 18 18 22 26 29 32 35 37 40 42
    Table C2 - Metric Units
Maximum Temperature Variation, °C Between Time of Solvent Welding and Final Use
   DEFLECTED PIPE
 OFFSET
LOOP LENGTH
OFFSET
     2 LOOP LENGTHS
   Loop Length Meters
Temperature Variation, °C
5° 10° 15° 20° 25° 30° 35° 40° 45° 50°
Offset- Millimeters
    5 65 83 95 105 114 123 133 143 154 164
15 164 219 266 307 343 377 409 440 469 498
30 314 424 522 609 687 758 823 884 943 999
      
























































   21   22   23   24   25