Page 14 - CPVC Fire Sprinkler Products Installation Instructions & Technical Handbook
P. 14

12 LISTINGS & APPROVALS
Figure 1 - Unfinished Basement, Solid Wood Joists, Center Wall Riser with Center Room Main
      MAIN
2x16 MAX.
BRANCH
8'-0" (2,4 m) MAX.
   16'-0" (4,9 m) MAX.
16'-0" (4,9 m) MAX.
   12" MAX. (304,8 mm) TO CENTER OF RISER
   8'-0" (2,4 m) MAX.
     RISER 1" MIN. TO 2" MAX.
    24" (609,6 mm) CENTERS
   1-3/4" (44,5 mm) MAX.
2'-0" MAX. (609,6 mm) TO PIPE SUPPORT
 40'-0" (12,2 m) MAX. TO WALL OR BLOCKING
 1-1/2" MAX. (38,1 mm) FROM WALL TO EDGE OF RISER
               Figure 2 - Unfinished Basement, Solid Wood Joists, Center Wall Riser with Main at Wall
       8'-0" (2,4 m) MAX.
MAIN
BRANCH
8'-0" (2,4 m) MAX.
40'-0" (12,2 m) MAX. TO WALL OR BLOCKING
              24" (609,6 mm) CENTERS
16'-0" (4,9 m) MAX.
16'-0" (4,9 m) MAX.
  12" (304,8 mm) MAX. TO CENTER OF RISER
 1-3/4" (44,5 mm) MAX.
   2x16 MAX.
2'-0" MAX. (609,6 mm) TO PIPE SUPPORT
    1-1/2" MAX. (38,1 mm) FROM WALL TO EDGE OF RISER
    RISER 1" MIN. TO 2" MAX.
   